J-SH(St)SH FE180 E30/E90, JE-H(StJ-SH(St)SH FE180 E30/E90, JE-H(St)H FE180/E30 HFFR ve JH(St)H…Lg HFFR type cables are used generally for fire alarm system.)H FE180/E30 HFFR ve JH(St)H…Lg HFFR type cables are used generally for fire alarm system.
J-SH (St) SH FE180 E30 / E90 Fire Alarm Cable
Under fire conditions (below 750 ° C heat and flame) hard work condition (FE-180) can be maintained at 180 minutes, energy transmission, fire resistant cables are halogen free. These cables in the fire alarm system, fire equipment required to work in, the control cables of the elevator and machine, the power cable in fire alarm system connected to the ventilation system in the desired environment of corrosive gases are burned during cable fire in hospitals, schools and office centers, and so on. Used in place.
CABLE STRUCTURE | |
Conductive | Finely stranded copper |
Insulation | Silicone rubber compounding |
Core identification | VDE 0815 |
Double | Two conductors bent to form a double |
twist | Pairs laid up in layers of optimum pitch |
Separator | polyester tape |
Screen | aluminum polyester with drain wire |
outer sheath | Very resistant to high temperatures and fire conditions halogen free silicone rubber compounding |
Sheath color | Orange |
Table 2.1: J-SH (St) SH FE180 E30 / E90 fire alarm cable construction
TECHNICIAL SPECIFICATIONS | |
Standard | According to VDE 0815 |
Insulation resistance | > 100 M x km |
Effective capacity (800 Hz) | 120 nF / km |
Operating voltage | 300V |
Test voltage (AC 50 Hz) | 800V |
Operating temperature | -60 ° C / + 180 ° C |
Min. bending radius | 7.5 x cable diameter |
flame tests | & IEC IEC 332.1 332.3 |
Insulation continuity (F 180) | IEC 331 (TS 3164 Ex-proof) |
Table 2.2: J-SH (St) SH FE180 E30 / E90 fire alarm cable specifications
JE-H (St) H FE180 / E30 HFF Fire Alarm Cable
Industrial facilities, major hotels, hospitals, shopping centers, power plants, cultural centers, housing, airports, subway, as the large number of people, automatic control to ensure the continuation of current flow in the fire at the plant, in the security and fire alarm systems with analog and digital signals used in transmission. Such cables do not conduct flame during fire, smoke density is so low it does not create a favorable environment for corrosion and does not remove the toxic gases to affect human health.
CABLE STRUCTURE | |
Conductive | Finely stranded copper |
Insulation | Halogen elastomer compounding |
Core identification | VDE 0815 |
Double | Two conductors bent to form a double |
twist | Pairs laid up in layers of optimum pitch |
Separator | polyester tape |
protective tape | Glass fiber textile tape |
Screen | AL-PES tape with drain wire |
outer sheath | HFF is compounding |
Sheath color | Orange |
Table 2.3: J-SH (St) SH FE180 E30 / E90 fire alarm cable specifications
TECHNICIAL SPECIFICATIONS | |
Standard | VDE 0815 |
Insulation resistance | > 100 Mohm.km |
Effective capacity (800 Hz) | 120 nF / km |
Operating voltage | 300 V |
Test voltage (AC 50 Hz) | 1200V |
Operating temperature | -30 ° C / + 70 ° C |
Min. bending radius | 15 x cable diameter |
flame test | IEC 332-1 & IEC 332-3 |
Insulation continuity (F 180 | IEC 331, TS 3164 |
Table 2.4: JE-H (St) H FE180 / E30 HFF fire alarm cable specifications
JH (St) H … Lg HFF Fire Alarm Cable
This halogen-free unshielded control and connecting cables are used in instrumentation and control engineering; In industrial electronics, computers, office machines; All communication systems, voice frequency transmission, data transmission and electronics for data communication and the fire is used as a warning cable. Such cables do not conduct flame during fire, smoke density is so low it does not create a favorable environment for corrosion and does not remove the toxic gases to affect human health.
CABLE STRUCTURE | |
Conductive | Mono stranded copper |
Insulation | HFF is compounding |
Core identification | VDE 0815 |
Double | Two conductors bent to form a double |
twist | Pairs laid up in layers of optimum pitch |
Separator | polyester tape |
Screen | AL-PES tape with drain wire |
outer sheath | HFF is compounding |
Sheath color | Red |
Table 2.5: JH (St) H … Lg HFF fire alarm cable construction
TECHNICIAL SPECIFICATIONS | |
Standard | VDE 0815 |
Insulation resistance | > 100 Mohm.km |
Effective capacity (800 Hz) | 120 nF / km |
Operating voltage | 300 V |
Test voltage (AC 50 Hz) | 800 V |
Operating temperature | -30 ° C / + 70 ° C |
Min. bending radius | 15 x cable diameter |
flame test | IEC 332-1 & IEC 332-3 |
Table 2.6: JH (St) H … Lg HFF fire alarm cable specifications
Fire Detection and Alarm Systems Issues to be Considered in Cabling
One of the most important reasons for not working as expected of a fire detection and alarm system wiring is done correctly and properly. Wiring in the assembly phase of design should be very careful about the following points.
– The zone where the detector (fire department) cables must be selected according to the manufacturer’s recommendation.
– The cable section must be calculated.
– Manufacturer zones (fire department) must be complied with in length.
– Cable load calculations must be performed.
– Connections must be made resistant manner and accurately.
– Cable routing should be selected so that it can be managed.
– It should not be water or very high humidity in the cable route. If the cable must be used in accordance with these terms.
– Cable shielding, standards and regulations must be grounded properly.